Conduit Fill Chart: How Many Wires Fit in EMT and PVC

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

Read your conduit size down the side and your wire size across the top for the largest number of THHN or THWN-2 conductors the NEC allows. Need the percentage for mixed sizes? Use the conduit fill calculator.

Maximum THHN/THWN-2 wires in EMT

These are the most same-size conductors allowed under NEC Chapter 9, Table 1 (40% fill for three or more wires), using the Table 4 conduit areas and Table 5 wire areas, with the Note 7 rule that rounds up when the result has a decimal of 0.8 or more. Count equipment grounding wires too.

Conduit1412108643211/02/0
1/2"129531111100
3/4"22161064211111
1"35261697433111
1-1/4"6145281612765432
1-1/2"84613822161087543
2"138101633626161311876

Maximum THHN/THWN-2 wires in PVC Schedule 40

Schedule 40 PVC has thicker walls than EMT, so the inside is a little smaller and the counts are the same or lower.

Conduit1412108643211/02/0
1/2"118531111000
3/4"2115954111111
1"34251596433111
1-1/4"6043271611765332
1-1/2"8259372115987543
2"13599623626161311876

What size conduit for a given number of wires?

Smallest EMT trade size that holds that many same-size THHN conductors:

Wires14 AWG12 AWG10 AWG8 AWG6 AWG
21/2"1/2"1/2"1/2"3/4"
31/2"1/2"1/2"1/2"3/4"
41/2"1/2"1/2"3/4"3/4"
51/2"1/2"1/2"3/4"1"
61/2"1/2"3/4"3/4"1"
71/2"1/2"3/4"1"1"
81/2"1/2"3/4"1"1-1/4"
91/2"1/2"3/4"1"1-1/4"
101/2"3/4"3/4"1-1/4"1-1/4"
111/2"3/4"1"1-1/4"1-1/4"
121/2"3/4"1"1-1/4"1-1/4"

Example: a 120 V circuit with a hot, neutral and ground is three conductors, which fit in 1/2 inch EMT even at 12 AWG. Six 12 AWG wires (two circuits with shared ground) also fit in 1/2 inch, and ten need 3/4 inch.

How the fill is calculated

Fill % = (number of wires × wire area) ÷ conduit internal area × 100

The limit is 53% for one wire, 31% for two and 40% for three or more. THHN wire areas used: 14 AWG 0.0097 in², 12 AWG 0.0133, 10 AWG 0.0211, 8 AWG 0.0366, 6 AWG 0.0507, 4 AWG 0.0824, 3 AWG 0.0973, 2 AWG 0.1158, 1 AWG 0.1562, 1/0 0.1855, 2/0 0.2223. Mixed sizes must be added up wire by wire with the calculator.

Fill is not derating. More than three current-carrying conductors in one conduit also lowers the ampacity under NEC 310.15. Run the size through the wire size calculator after you choose the conduit.

Frequently asked questions

How many 12 gauge wires fit in 1/2 inch conduit?

Nine THHN conductors in 1/2 inch EMT, or eight in 1/2 inch Schedule 40 PVC.

How many 10 gauge wires fit in 3/4 inch conduit?

Ten THHN conductors in 3/4 inch EMT. Check the table for PVC, which holds slightly fewer.

Does the ground wire count?

Yes. Equipment grounding conductors count for fill, but not for current-carrying derating.

What is the NEC fill limit?

53% for one conductor, 31% for two and 40% for three or more, from Chapter 9, Table 1.

Sources

Calculators for this

Last updated November 11, 2026. Values follow published tables. How we check our data. Found an error? Tell us.