Wire Gauge Chart: AWG Size, Diameter and Amps

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

Find your gauge in the first column and read across for the bare-wire diameter, the cross-section area, the circular mils and the copper ampacity. The smaller the gauge number, the thicker the wire. To pick a size for a real circuit, use the wire size calculator.

AWG wire gauge size chart

AWG is the American Wire Gauge. Diameters are for solid bare copper and follow the AWG formula: each step down the scale multiplies the diameter by 1.1229. The ampacity column is the NEC Table 310.16 value for copper at 75°C, the column most circuit breakers and panels use.

AWGDiameter (in)Diameter (mm)Area (mm²)Circular milsCopper amps (75°C)
4/00.460011.684107.22211,600230 A
3/00.409610.40585.03167,800200 A
2/00.36489.26667.43133,100175 A
1/00.32498.25153.48105,600150 A
10.28937.34842.4183,690130 A
20.25766.54433.6366,360115 A
30.22945.82726.6752,620100 A
40.20435.18921.1541,74085 A
60.16204.11513.3026,24065 A
80.12853.2648.3716,51050 A
100.10192.5885.2610,38035 A
120.08082.0533.316,53025 A
140.06411.6282.084,11020 A
160.05081.2911.312,580n/a
180.04031.0240.821,620n/a
200.03200.8120.521,022n/a
220.02530.6440.33642n/a
240.02010.5110.20404n/a
260.01590.4050.13254n/a
280.01260.3210.08160n/a
300.01000.2550.05101n/a

14 AWG copper is limited to 15 A, 12 AWG to 20 A and 10 AWG to 30 A, and 12 and 10 AWG aluminum to 15 A and 25 A, by the overcurrent rules in NEC 240.4(D), even where the ampacity table lists more.

Sizes smaller than 14 AWG are not listed in Table 310.16, which covers building wire. They are used for low-voltage, control and electronic wiring.

How wire gauge works

Gauge numbers run backwards: 4 AWG is much thicker than 14 AWG. Two rules of thumb help you check any table:

Sizes larger than 4/0 (pronounced "four-aught") switch to kcmil, thousands of circular mils, starting at 250 kcmil. A circular mil is the area of a circle one thousandth of an inch across.

Which gauge for which job?

GaugeTypical useCopper limit
14 AWGLighting and 15 A receptacle circuits15 A
12 AWG20 A circuits: kitchen, bath, garage, general receptacles20 A
10 AWG30 A circuits: dryers, water heaters, small AC units30 A
8 AWG40 to 50 A circuits: ranges, EV chargers, large AC50 A at 75°C
6 AWG50 to 60 A: ranges, sub panels, hot tubs65 A at 75°C
4 AWG60 to 85 A: sub panels, 100 A dwelling service85 A at 75°C

These are minimums for ampacity only. Long runs need a larger wire to keep voltage drop in check, and bundling or hot locations cut the ampacity. See the breaker to wire size chart for the full list by breaker rating and the amps per wire size table for every gauge in all three temperature columns.

Solid, stranded and the metric sizes

Solid wire is one piece of copper and is common in house wiring up to 10 AWG. Stranded wire is many thin strands, more flexible and standard above 8 AWG and for cords. Stranded wire of the same gauge has the same copper area but a slightly larger overall diameter. Metric cable is sold by area: use the AWG to mm chart to convert.

Frequently asked questions

What is the thickest wire gauge?

In the AWG system, 4/0 (0000) is the thickest named gauge at 0.46 inches, or 11.7 mm. Larger conductors are sold in kcmil sizes such as 250 and 500 kcmil.

Is a lower gauge number thicker?

Yes. A 10 gauge wire is thicker than a 14 gauge wire and carries more current.

What gauge wire do I need for 20 amps?

12 AWG copper. 14 AWG is limited to 15 amps.

What is the difference between AWG and SWG?

AWG is the American standard. SWG, the British Standard Wire Gauge, is an older system with different diameters for the same number, so do not use the two interchangeably.

Sources

Calculators for this

Last updated November 11, 2026. Values follow published tables. How we check our data. Found an error? Tell us.