Ground Wire Size Calculator

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

Pick the breaker or fuse rating and the ground wire material. The calculator returns the minimum equipment grounding conductor from NEC Table 250.122 and applies the 250.122(B) increase when you upsized the hot wires for voltage drop.

Change this only if you upsized the hot wires for voltage drop.
12 AWG
Ground wire size
12 AWG
Table 250.122 minimum
12 AWG (75°C)
Standard hot wire (copper)

NEC Table 250.122: ground wire size by breaker rating

The equipment grounding conductor (EGC) is the bare, green or green-with-yellow wire that carries fault current back to the panel so the breaker trips. NEC 250.122 sizes it from the rating of the breaker or fuse protecting the circuit, not from the load. Find the first row whose rating is not smaller than your breaker.

Breaker or fuse up toCopper groundAluminum ground
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1,000 A2/0 AWG4/0 AWG
1,200 A3/0 AWG250 kcmil
1,600 A4/0 AWG350 kcmil
2,000 A250 kcmil400 kcmil

Table 250.122 continues above 2,000 A. A 30 A or 40 A or 50 A breaker uses the 60 A row, so the ground is 10 AWG copper. A 70 A to 100 A breaker uses 8 AWG copper.

Example

A 50 A electric range circuit with 6 AWG hot wires needs a 10 AWG copper ground, because 50 A falls in the 60 A row. A 20 A kitchen circuit needs 12 AWG, which is why 12/2 NM cable has a 12 AWG bare ground. The ground is never required to be larger than the hot conductors (250.122(A)).

Upsizing the ground when you upsize the hot wires

If you increase the hot conductors for any reason other than ambient temperature or bundling, 250.122(B) says the ground must grow in proportion. Long runs sized for voltage drop are the usual case. The calculator multiplies the Table 250.122 circular-mil area by the ratio of the installed hot wire to the standard hot wire, then rounds up to the next size.

Example: a 20 A circuit normally uses 12 AWG (6,530 circular mils). Running 8 AWG (16,510 circular mils) for distance gives a ratio of 2.53, so the ground becomes 8 AWG copper too. Use the voltage drop calculator to decide whether you need the larger hot wire at all.

Service grounding electrode conductor (NEC Table 250.66)

A different table sizes the wire that runs from the main panel to the ground rod, water pipe or concrete-encased electrode. It depends on the size of the service-entrance conductors, not the breaker:

Largest copper service conductorCopper electrode wireAluminum electrode wire
2 AWG or smaller8 AWG6 AWG
1 AWG or 1/06 AWG4 AWG
2/0 or 3/04 AWG2 AWG
Over 3/0 through 350 kcmil2 AWG1/0 AWG
Over 350 through 600 kcmil1/0 AWG3/0 AWG

A typical 200 A dwelling service uses 2/0 copper (or 4/0 aluminum) conductors, so the electrode wire is 4 AWG copper. If the wire goes only to a ground rod, 250.66(A) does not require more than 6 AWG copper, and to a concrete-encased electrode it need not exceed 4 AWG copper. See the 200 amp service wire size guide for the full set.

Two different grounds. The equipment grounding conductor (Table 250.122) rides with the circuit and is sized by the breaker. The grounding electrode conductor (Table 250.66) connects the system to earth and is sized by the service conductors. Mixing them up is the most common ground wire sizing mistake.

Frequently asked questions

What size ground wire for a 20 amp circuit?

12 AWG copper, or 10 AWG aluminum. That is the Table 250.122 row for breakers up to 20 A.

What size ground wire for a 50 amp breaker?

10 AWG copper or 8 AWG aluminum, because 50 A falls in the 60 A row of the table.

What size ground wire for a 100 amp panel?

For a 100 A feeder breaker the equipment ground is 8 AWG copper or 6 AWG aluminum. The grounding electrode conductor at a 100 A service depends on the service wire size: usually 8 AWG copper.

Can the ground wire be smaller than the hot wires?

Yes, in the normal case. The 250.122 table gives smaller sizes than the circuit conductors above 15 A. The ground is not required to be larger than the hot wires, and must be increased only if the hot wires are upsized.