12V Wire Gauge Chart: Wire Size by Amps and Distance

By Hassan Nawaz, B.Sc. Electrical Engineering. Updated November 11, 2026.

For a 20 A load 10 ft from a 12 V battery, use 8 AWG copper. The charts below show the smallest AWG that stays within the voltage drop limit for 5 to 100 amps and 5 to 50 feet. Distance is one way, from the battery or fuse block to the load. For your own numbers, use the wire size calculator with the system set to DC.

12 V wire gauge at 3% voltage drop

Each cell is the smallest copper AWG size that carries the current and keeps the drop at or below 3% of 12 V, which is 0.36 V across the whole round trip. The charts use the voltage drop formula VD = 2 × 12.9 × I × L ÷ circular mils, and an ampacity floor from the NEC 75°C column (7 A for 18 AWG and 10 A for 16 AWG under 240.4(D)).

Load5 ft10 ft15 ft20 ft25 ft30 ft40 ft50 ft
5 A1614121010886
10 A1410886644
15 A128864432
20 A108644321
30 A8643221/02/0
40 A843211/02/03/0
50 A64211/02/03/04/0
60 A6321/02/02/04/0>4/0
80 A421/02/03/04/0>4/0>4/0
100 A312/03/04/0>4/0>4/0>4/0

Example: a 30 A load 20 ft away needs 3 AWG. A 10 A load 10 ft away needs 10 AWG, and a 5 A load 5 ft away only 16 AWG.

12 V at 10% drop (loads that tolerate it)

Some loads, such as pumps, fans and some lighting, tolerate more drop. If the equipment allows a lower voltage and you accept the lost power, the wire can be smaller. Check the equipment's minimum voltage first, because a loaded battery already sits below 12.6 V.

Load5 ft10 ft15 ft20 ft25 ft30 ft40 ft50 ft
5 A1818181614141212
10 A161614121212108
15 A14141212101088
20 A121212108866
30 A10101088664
40 A88866643
50 A88864432
60 A66664432
80 A44443311/0
100 A3333221/02/0

24 V at 3% voltage drop

Doubling the voltage halves the current for the same watts and cuts the percentage drop by four for the same wire. That is why larger solar, RV and boat systems use 24 V or 48 V.

Load5 ft10 ft15 ft20 ft25 ft30 ft40 ft50 ft
5 A1816141412121010
10 A1614121010886
15 A14121088864
20 A1210886644
30 A108864432
40 A88644321
50 A86443211/0
60 A6643221/02/0
80 A443211/02/03/0
100 A33211/02/03/04/0

How to size a 12 V wire

  1. Find the amps: watts ÷ 12. A 240 W load is 20 A (see the watts to amps chart).
  2. Measure the one-way distance from the power source to the load along the actual route.
  3. Read the size from the table, or step up one size for continuous loads, warm locations or a long bundle.
  4. Fuse the wire at its source, rated at or below the wire's ampacity.
Use copper and the right wire type. The tables assume copper conductors. Copper-clad aluminum and thin-strand welding or battery cable can have more resistance than the K value used here. Wiring in vehicles and boats follows its own standards, so confirm the rules for yours.

Frequently asked questions

What gauge wire for 12V 20 amps?

8 AWG copper for runs up to about 11 ft at 3% drop, 6 AWG up to about 18 ft and 4 AWG up to about 29 ft. 12 AWG carries 20 A but drops too much voltage beyond about 4.5 ft.

What size wire for 12V 30 amps?

6 AWG for up to about 12 ft at 3% drop, and 4 AWG for up to about 19 ft.

How far can I run 12 gauge wire at 12 volts?

At 10 A, about 9 ft one way within 3% drop. At 5 A, about 18 ft. At 15 A, about 6 ft.

Is 3% voltage drop necessary?

The NEC recommends 3% for branch circuits, and 3% is a good target for electronics and lights. Check the minimum voltage your equipment accepts before allowing more.